Liên hệ 0907080979
Mã SP: ACP2-4
System fuse: 5 Amp self-resetting polyfuse
Mains fuse: 20mm 3 Amp
Operating Temperature: -5 to +50° C
Thông tin chi tiết
| Construction | 1.2mm mild sheet steel |
|---|---|
| IP Rating | IP30 |
| Finish | Epoxy powder coated |
| Colour – lid & box | BS 00 A 05 grey – fine texture |
| Colour – controls plate & labels | RAL 7047 light grey – satin |
| Display | 8 lines of 40 characters graphic LCD |
| Detection circuits (Loops) | 2 or 4 (400mA each) |
| Zone LED’s | 0, 16, 48, or 96 (up to 500 software zones) |
| 4 sounder circuits | Each fused at 1 Amp (total load 2 Amp) |
| Fire contact | Volt free 1 Amp 30V DC |
| Alarm contact | Volt free 1 Amp 30V DC |
| Fault contact | Volt free 1 Amp 30V DC |
| Programmable relay 1 | Volt free 1 Amp 30V DC |
| Programmable relay 2 | Volt free 1 Amp 30V DC |
| Fire routing output | Monitored-voltage reversing, fused at 500mA |
| Fault routing output | Monitored-voltage reversing, fused at 500mA |
| Extinguisher output | Monitored-voltage reversing, fused at 1A |
| Fault input | Volt free contact input signals fault |
| Reset input | Volt free contact input resets panel |
| Intermittent input | Volt free contact input pulses sounder outputs |
| Continuous input | Volt free contact input for continuous sounders |
| Silence input | Volt free contact input silences sounders |
| Programmable input 1 | Volt free contact for any action required |
| Programmable input 2 | Volt free contact for any action required |
| Programmable input 3 | Volt free contact for any action required |
| Auxiliary 24V DC output | Fused at 500mA |
| System fuse | 5 Amp self-resetting polyfuse |
| Mains fuse | 20mm 3 Amp |
| Operating Temperature | -5 to +50° C |
| Operating humidity | To 95% (non-condensing) |
| Mains voltage supply | 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V) |
| Battery (24 hour standby) | 12Ah 12V (2 per panel) (non-networked) |
| Day/night modes | 2 with variable device sensitivity |
| Input delays | Individual for each device selectable up to 2 minutes |
| Output delays | Individual 2-stage to 10 minutes per stage |
| 2 programmable function buttons | Programmable to carry out any cause & effect, disablement or test action |
| 3 programmable indicators | Red/yellow/green to indicate any action |
| Network (option) | Up to 64 panels on 2 wires (SEN-MX5801 Network Card required) |
| Printer (option) | New front loading feature |
| Download lead | SEN-MX5807 (standard) or SEN-MX5806 (economy) |
| Weight | 10kg (standard panel) |