Thông tin chi tiết
- The input module serves as an interface to transmit alarms or technical signals from other equipments to the fire alarm control unit.
- Connected to the F-Bus‚ device address can be set with a DIP-switch.
- Serves as interface for potential free signals from flow switches‚ pressure switches etc. to the fire alarm system.
- The signal will be transmitted to the controller and trigger corresponding actions.
- Connection faults will be automatically detected and displayed on the controller.
- Operating voltage 18… 26 VDC
- Operating temperature 0… +49 °C
- Relative humidity ≤93 % (32 ± 2 °C)
- Activation current ≤3.2 mA
- Quiescent current ≤1 mA
- Wiring capacity 1.0…1.5 mm²
- EOL EOL82
Khi có nhu cầu Siemens các bạn hãy nhanh tay liên hệ với chúng tôi
CÔNG TY CỔ PHẦN TM-XD PCCC QUỐC AN
Đ/c: 212 Cộng Hòa – P.12 – Q.Tân Bình – TP.HCM
Tel : (028) 2247.1234 – 22.411.113
Email: sales@quocanpccc.com
Website: quocanpccc.com / thietbipccc24h.com